PRO AUTOCAL 230 power pac

PRO AUTOCAL 230 power pac with 230 VAC, PRO-Shield protection with continuous LED status light, auto calibration and function test, hazardous location approved, C/US listed for Class II, Groups E, F, G

Need assistance faster?
Give us a call Monday - Friday
8:00am - 5:00pm CST

Phone: (402) 434-9102
Email: [email protected]

Get a quote

The person responsible for your area will be in touch shortly

PRO AUTOCAL: Calibration Without Opening the Unit

This capacitance sensor allows for simple, automatic calibration using a special magnet. No need to remove the unit cover!

Want a capacitance probe that sets up fast? Temperature-stable calibration and external testing can be performed in just minutes.

Get unsurpassed 0.5 pF sensitivity and fail-safe performance with the PRO AUTOCAL. Plus, an adjustable time delay of up to 10 seconds allows for settling of material--virtually eliminating false alarms.

What else you get with PRO AUTOCAL:

  • PRO-Shield compensates for material buildup to guard against false readings
  • Operates below RF range, always free from RF interference
  • Switch selectable high/low fail-safe safeguards from failures
  • Delrin or Teflon sleeved, bare, food grade, flush mount, or flexible probes
  • Visual LED indicates sensor status of uncovered, covered, or power failure

How and where to use PRO AUTOCAL:

  • As a point level detection and process control for solid, liquids, or slurries 
  • Aggressive materials such as coal or fly ash; power, mining, and foundries
  • Processing of plastics, chemicals, foodstuffs, or pharmaceuticals
  • Milling operations processing feed, grain, wood, or paper
pro-autocal-capacitance-probe
More Information
SKUPA2.
Means of MeasurementCapacitance
Measurement TypePoint Level
MediumSolids
Voltage 230 VAC
OutputsRelay DPDT 10 Amp - 250 VAC max
Ambient Temperature-40°F to +185°F (-40°C to +85°C)
Process TemperatureUp to +176°F (80°C)
ApprovalsCSA Class II, Groups E, F & G
Enclosure TypeNEMA 4X, NEMA 5, NEMA 9, NEMA 12
Enclosure MaterialDie cast aluminum
Mounting1.25" NPT
Conduit Entry0.75" NPT